====== NUT (Network UPS Tool) ====== ====== NUT (Network UPS Tool) ======
Instruction for installation of Network UPS Tools (NUT) on fun_plug v 0.5. These instructions are based on information found at the Network UPS Tool website ([[http://networkupstools.org/doc/2.2.0/INSTALL.html]]). Instruction for installation of Network UPS Tools (NUT) on fun_plug v 0.5. These instructions are based on information found at the Network UPS Tool website ([[http://networkupstools.org/doc/2.2.0/INSTALL.html]]).
 +
 +====== Summary ======
 +The primary goal of the Network UPS Tools (NUT) project is to provide reliable monitoring of UPS and PDU hardware and ensure safe shutdowns of the systems which are connected.
 +We attempt to monitor every kind of UPS and PDU, given sufficient interest.  Summary from [[http://networkupstools.org|NUT project page]].
 +
===== Getting Started ===== ===== Getting Started =====
-==== What's Needed ==== 
-A DNS323 with Fun_Plug 0.5 installed. 
-A functional telnet connection. 
 +
 +==== What's Needed ====
Successful installation of NUT requires three packages from fonz's website ([[http://www.inreto.de/dns323/fun-plug/0.5/packages/]]). They are; Successful installation of NUT requires three packages from fonz's website ([[http://www.inreto.de/dns323/fun-plug/0.5/packages/]]). They are;
  * libusb-0.1.12-1.tgz;   * libusb-0.1.12-1.tgz;
  * neon-0.25.5-1.tgz and;   * neon-0.25.5-1.tgz and;
-  * nut-2.2.2-2.tgz+  * nut-2.2.2-3.tgz 
 + 
 + 
 +=== Assumptions === 
 +DNS323 is operating with Firmware version 1.05 or 1.06 (Installation has not been tested with other firmware versions). 
 + 
 +Fun_Plug 0.5 installed and operable. 
 + 
 +A functional telnet connection. 
 + 
 + 
 + 
Line 24: Line 40:
rsync -av inreto.de::dns323/fun-plug/0.5/packages/neon-0.25.5-1.tgz . rsync -av inreto.de::dns323/fun-plug/0.5/packages/neon-0.25.5-1.tgz .
rsync -av inreto.de::dns323/fun-plug/0.5/packages/libusb-0.1.12-1.tgz . rsync -av inreto.de::dns323/fun-plug/0.5/packages/libusb-0.1.12-1.tgz .
- rsync -av inreto.de::dns323/fun-plug/0.5/packages/nut-2.2.2-2.tgz .+ rsync -av inreto.de::dns323/fun-plug/0.5/packages/nut-2.2.2-3.tgz . 
Line 32: Line 49:
funpkg -i neon-0.25.5-1.tgz funpkg -i neon-0.25.5-1.tgz
funpkg -i libusb-0.1.12-1.tgz funpkg -i libusb-0.1.12-1.tgz
- funpkg -i nut-2.2.2-2.tgz+ funpkg -i nut-2.2.2-3.tgz
Line 68: Line 85:
===== Configure and Start NUT Driver ===== ===== Configure and Start NUT Driver =====
 +
==== Create ups.conf File ==== ==== Create ups.conf File ====
During NUT installation sample configuration files were copied to the /ffp/etc directory. These files are identifiable by their ''.sample'' suffix. During this step of the configuration process a ups.conf file will be created from the ups.conf.sample file. This is achieved by copying the sample ups configuration file to the /ffp/etc directory. The command to do so follows; During NUT installation sample configuration files were copied to the /ffp/etc directory. These files are identifiable by their ''.sample'' suffix. During this step of the configuration process a ups.conf file will be created from the ups.conf.sample file. This is achieved by copying the sample ups configuration file to the /ffp/etc directory. The command to do so follows;
- cp /ffp/etc/ups.conf.sample /ffp/etc/ups.conf+ cp /ffp/etc/examples/nut/ups.conf.sample /ffp/etc/ups.conf 
 + 
==== Add Driver Configuration Detail ==== ==== Add Driver Configuration Detail ====
-Prior to modifying the ups.conf file you'll need to determine which driver is used with your specific UPS. A UPS hardware compatibility list is located on the [[http://www.networkupstools.org/compat/stable.html|Network UPS Tools]] website. Review this list to determine which driver is required for your specific application. Please note these instructions pertain specifically to USB connected UPS. +Prior to modifying the ups.conf file you'll need to determine which driver is used with your specific UPS. A UPS hardware compatibility list is located on the [[https://networkupstools.org/stable-hcl.html]] website. Review this list to determine which driver is required for your specific application. Please note these instructions pertain specifically to USB connected UPS.
Use your favourite editor (I use Notepad++) to open the ups.conf file, enter and subsequently save your specific settings. Use your favourite editor (I use Notepad++) to open the ups.conf file, enter and subsequently save your specific settings.
Line 107: Line 127:
During this step of the configuration process a upsd.conf file will be created from the upsd.conf.sample file. This is achieved by copying the sample upsd configuration file to the /ffp/etc directory. The command to do so follows; During this step of the configuration process a upsd.conf file will be created from the upsd.conf.sample file. This is achieved by copying the sample upsd configuration file to the /ffp/etc directory. The command to do so follows;
- cp /ffp/etc/upsd.conf.sample /ffp/etc/upsd.conf+ cp /ffp/etc/examples/nut/upsd.conf.sample /ffp/etc/upsd.conf
=== Configuring Specific Host Settings === === Configuring Specific Host Settings ===
Line 120: Line 140:
During this step of the configuration process a upsd.users file will be created from the upsd.users.sample file. This is achieved by copying the sample upsd configuration file to the /ffp/etc directory. The command to do so follows; During this step of the configuration process a upsd.users file will be created from the upsd.users.sample file. This is achieved by copying the sample upsd configuration file to the /ffp/etc directory. The command to do so follows;
- cp /ffp/etc/upsd.users.sample /ffp/etc/upsd.users+ cp /ffp/etc/examples/nut/upsd.users.sample /ffp/etc/upsd.users
=== Configuring an Administrative User === === Configuring an Administrative User ===
Line 144: Line 164:
The Network Server can be stopped by issuing an ''upsd -c stop'' command. The Network Server can be stopped by issuing an ''upsd -c stop'' command.
 +
 +
==== UPS and Server Status Check ==== ==== UPS and Server Status Check ====
Line 164: Line 186:
battery.date: 2001/09/25 battery.date: 2001/09/25
battery.mfr.date: 2008/06/05 battery.mfr.date: 2008/06/05
- battery.runtime: 2025+ battery.runtime: 2535
battery.runtime.low: 120 battery.runtime.low: 120
- battery.temperature: 3022999999999998800+ battery.temperature: 29.2
battery.type: PbAc battery.type: PbAc
battery.voltage: 27.8 battery.voltage: 27.8
battery.voltage.nominal: 24.0 battery.voltage.nominal: 24.0
 + device.mfr: American Power Conversion
 + device.model: Back-UPS RS 900
 + device.serial: 5B0743U08220
 + device.type: ups
driver.name: usbhid-ups driver.name: usbhid-ups
driver.parameter.pollfreq: 30 driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2 driver.parameter.pollinterval: 2
- driver.parameter.port: auto + driver.parameter.port: AUTO 
- driver.version: 2.2.2 + driver.version: 2.4.1 
- driver.version.data: APC HID 0.92 + driver.version.data: APC HID 0.93 
- driver.version.internal: 0.33+ driver.version.internal: 0.34
input.voltage: 122.0 input.voltage: 122.0
input.voltage.nominal: 120 input.voltage.nominal: 120
Line 183: Line 209:
ups.beeper.status: enabled ups.beeper.status: enabled
ups.delay.shutdown: 20 ups.delay.shutdown: 20
- ups.delay.start: 30 
ups.firmware: 9.o2 .D ups.firmware: 9.o2 .D
ups.firmware.aux: o2 ups.firmware.aux: o2
- ups.load:22999999999999994+ ups.load: 18.0
ups.mfr: American Power Conversion ups.mfr: American Power Conversion
ups.mfr.date: 2007/10/24 ups.mfr.date: 2007/10/24
Line 202: Line 227:
During this step of the configuration process a upsmon.conf file will be created from the upsmon.conf.sample file. This is achieved by copying the sample upsmon configuration file to the /ffp/etc directory. The command to do so follows; During this step of the configuration process a upsmon.conf file will be created from the upsmon.conf.sample file. This is achieved by copying the sample upsmon configuration file to the /ffp/etc directory. The command to do so follows;
- cp /ffp/etc/upsmon.conf.sample /ffp/etc/upsmon.conf+ cp /ffp/etc/examples/nut/upsmon.conf.sample /ffp/etc/upsmon.conf
==== Configure a RUN_AS_USER ==== ==== Configure a RUN_AS_USER ====
Line 243: Line 268:
chmod 0770 /ffp/var/state/ups chmod 0770 /ffp/var/state/ups
-===== Automating the Startup Process =====+ 
 + 
 + 
 + 
 +====== Automating the Startup Process ======
You can Telnet to the DNS323 each time you want to start NUT or use a startup script. The following can be added to a nut.sh script file and stored in the /ffp/start directory by copying the content of the code box into your favourite editor then saving the resultant file as /ffp/start/nut.sh. You can Telnet to the DNS323 each time you want to start NUT or use a startup script. The following can be added to a nut.sh script file and stored in the /ffp/start directory by copying the content of the code box into your favourite editor then saving the resultant file as /ffp/start/nut.sh.
 +
 +Use this script for DNS323 firmware versions prior to 1.07.
#!/ffp/bin/sh #!/ffp/bin/sh
- # PROVIDES: nut+ # PROVIDE: nut
. /ffp/etc/ffp.subr . /ffp/etc/ffp.subr
Line 282: Line 313:
run_rc_command "$1" run_rc_command "$1"
 +
 +Use this script for DNS323 firmware version 1.07.
 +
 + #!/ffp/bin/sh
 +
 + # PROVIDE: nut
 +
 + . /ffp/etc/ffp.subr
 +
 + name="nut"
 + start_cmd="nut_start"
 + stop_cmd="nut_stop"
 +
 + nut_start()
 + {
 + #####################
 + # We're using NUT UPS from ffp; #
 + #####################
 +
 + ############################################
 + # Stop built in NUT UPS deamons in preparation for starting ffp NUT UPS #
 + ############################################
 + if ps | grep /usr/local/ups/bin/usbhid-ups | grep -v grep
 + then
 + echo "* Stopping Default UPS Services"
 + # Stop NUT Network Server
 + /sys/crfs/sbin/upsd -c stop
 +
 + # Stop NUT driver for UPS hardware.
 + /sys/crfs/sbin/upsdrvctl stop
 + fi
 +
 + sleep 2
 +
 + ##############
 + # Start ffp NUT UPS #
 + ##############
 + # Start NUT driver for UPS hardware.
 + /ffp/bin/upsdrvctl start
 +
 + # Start NUT Network Server
 + /ffp/sbin/upsd
 +
 + # Start NUT monitor agent
 + /ffp/sbin/upsmon -u monuser
 + }
 +
 + nut_stop()
 + {
 + # Stop NUT monitor agent
 + /ffp/sbin/upsmon -c stop
 +
 + # Stop NUT Network Server
 + /ffp/sbin/upsd -c stop
 +
 + # Stop NUT driver for UPS hardware.
 + /ffp/bin/upsdrvctl stop
 + }
 +
 + run_rc_command "$1"
 +
 +Don't forget to make it runnable:
 +
 + chmod a+x /ffp/start/nut.sh